RCD Test Intervals

Indicative testing and inspection intervals for electrical equipment *

RCD Indicative testing and inspection interval table*

(CAUTION: This page must be read in conjunction with AS/NZS 3760 as a whole, and particularly 2.1)

 

Type of environment and/or  equipment

Push-button test - by user

Operating time and push-button test

Portable

Fixed

Portable

Fixed

1

Factories, workshops, places of manufacture, assembly, maintenance or fabrication.

Daily, or before every use, whichever is the longer

6 months

12 months

12 months

2

Environment where the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment

3 months

6 months

12 months

12 months

3

Environment where the equipment or supply cord is NOT subject to flexing in normal use and is NOT  open to abuse and is NOT in a hostile environment

3 months

6 months

2 years

2 years

* Source: Extract from table 4 AS/NZS 3760

 